• Product Details
  • Additional Information
  • Inquiry

Product Description

1. Overview

 

The JGHD4 medium voltage circuit breaker uses sulfur hexafluoride(SF6) gas as an arc extinguishing and insulating medium. SF6 gas has a smooth breaking characteristic, in which no current cut-off phenomenon occurs when breaking the current, and no operating over voltage is generated. This excellent characteristic ensures that the circuit breaker has a long electrical life. And the impact, dielectric level and thermal stress on the equipment during operation will not be affected. The pole of the circuit breaker, that is, the arc extinguishing chamber part, is a closed system that is maintenance-free for life. Its sealing life meets the IEC 62271-100 and CEI 17-1 1375 standards. The opening/closing process of the JGHD4 circuit breaker is completed by the REH type spring operating mechanism.

The operating mechanism and the pole are fixed on the same metal frame. It also serves as a trolley, which can be pushed in and out along the guide rail in the switchgear. The trolley movement can be operated when the cabinet door is closed.

The lightweight and compact circuit breaker structure ensures its sturdiness and reliability.

The JG series automatic reclosing device integrates control, protection, measurement, communication, fault detection, and online monitoring of closing and opening.

 

2. Features

Ø Automatic buffer breaking technology

Ø Arc extinguishing without chopping

Ø No reignition after disconnection

Ø Extinguishing method for rapid recovery of dielectric properties

Ø Withstands insulation voltage even at zero relative pressure (*)

Ø Up to 30% of rated breaking capacity even at zero relative pressure (*)

Ø Lifetime sealed poles

Ø Three gas tightness check tests for each device

Ø Compact dimensions

Ø Fixed and withdrawable

Ø Energy storage operating mechanism with anti-tripping device as standard

Ø Entire circuit breaker range

Ø Mechanical safety lock to prevent incorrect operation

Ø Simple personalization thanks to a complete range of accessories

Ø Maintenance-free

Ø SF6 gas pressure control device (on request).

 

3. Applications

 

JGHD4 circuit breakers can be used for the control and protection of distribution lines, substations, distribution stations, motors, transformers and capacitor banks.

Due to the use of SF6 automatic buffer breaking technology, JGHD4 circuit breakers will not generate operating over voltage, so they are very suitable for use in places that are particularly sensitive to the dielectric strength level of insulating materials, especially for capacitor banks, compensating reactors, motors and other capacitive and inductive load applications.

 

4. Arc extinguishing technology

The arc extinguishing principle of JGHD4 circuit breaker is based on thermal expansion (self-energy type) + compressed air blowing. Regardless of the current value, it can ensure that the arc is gradually extinguished, and the arcing time is short, without current cutoff and reignition.

JGHD4 series products use the thermal expansion + compressed air blowing arc extinguishing technology that has been maturely used in the field of high-voltage switches, giving it an advantage in medium-voltage switches.

 

5. Main technical data

SF6 circuit breaker


JGHD4-12

JGHD4-17

JGHD4-24

JGHD4-36

JGHD4-40

Standard


IEC 62271-100 CEI 17-1 1375

Rated voltage

Ur [kV]

12

17.5

24

36

40.5

Rated insulation voltage

Us [kV]

12

17.5

24

36

40.5

50 Hz (1 minute) power frequency withstand voltage

Ud [kV]

28

38

50

70

95

Pulse withstand voltage

Up [kV]

75

95

125

170

185

Rated frequency

Fr [Hz]

50/60

Rated operating current (40 °C)

Ir [A]

630/800/1250/1600/2000/2500/3150/3600

Rated breaking capacity

Isc [kA]

12.5/16/25/31.5/40/50

Rated short-time withstand current

Ik [kA]

12.5/16/25/31.5/40/50

Rated short-circuit closing current

Ip [kA]

31.5/40/50/63/80/100/125

Rated operating sequence


O-0.3s-CO-15s-CO

Breaking time

[ms]

45

45

45

45

45

Arc burning time

[ms]

10~15

10~15

10~15

10~15

10~15

Opening time

[ms]

55~60

55~60

55~60

55~60

55~60

Closing time

[ms]

80

80

80

80

80

Maximum overall dimensions

 

H [mm]

640

649

818

730/1060

790/1123

W[mm]

493

618

730

880/955

748/805

D [mm]

496

496

620

695

833

Pole center distance

I [mm]

150

210

275

350

275

Weight

[kg]

114

114

119

128

190

SF6 gas absolute pressure

[kPa]

380

380

380

380

450

Operating environment temperature

[°C]

-5~+40

Humid tropical type electrical appliances


IEC:    60068-2-30, 60721-2-1

Electromagnetic compatibility


IEC: 60694






Related Products

Leave A Message

Copyright © 2021 By JGGY Electrical.com